PT Wijayamas Teknindo

sql
Fluke 1555 And 1550C Insulation Resistance Testers
Fluke 1555 And 1550C Insulation Resistance Testers
Hover to Zoom

Last Updated
28 Mar 2016
Country Origin
United States
Minimum Order
1

Specification of

Fluke 1555 And 1550C Insulation Resistance Testers

Electrical Specifications
The tester's accuracy is specified for one year after calibration at operating temperatures of 0 °C to 35 °C. For operating temperatures outside the range (-20 °C to 0 °C and 35 °C to 50 °C), add ± .25 % per °C, except on the 20 % bands add ± 1 % per °C.
Insulation Resistance Measurement
Test voltage (DC)RangeAccuracy (± reading)
250 V< 200 kΩ Unspecified
200 kΩ to 5 GΩ 5 %
5 GΩ to 50 GΩ 20 %
> 50 GΩ Unspecified
500 V< 500 kΩ Unspecified
500 kΩ to 10 GΩ 5 %
10 GΩ to 100 GΩ 20 %
> 100 GΩ Unspecified
1000 V< 200 kΩ Unspecified
200 kΩ to 20 GΩ 5 %
20 GΩ to 200 GΩ 20 %
> 200 GΩ Unspecified
2500 V< 200 kΩ Unspecified
200 kΩ to 50 GΩ 5 %
50 GΩ to 500 GΩ 20 %
> 500 GΩ Unspecified
5000 V< 200 kΩ Unspecified
200 kΩ to 100 GΩ 5 %
100 GΩ to 1 TΩ 20 %
> 1 TΩ Unspecified
10000 V (1555 Only)< 200 kΩ Unspecified
200 kΩ to 200 GΩ 5 %
200 GΩ to 2 TΩ 20 %
> 2 TΩ Unspecified
Bar graph range 0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy -0 %, +10 % at 1 mA load current
Induced ac mains current rejection 2 mA maximum
Charging rate for capacitive load 5 seconds per μF
Discharge rate for capacitive load 1.5 s/μF
Leakage current measurement Range: 1 nA to 2 mA
Accuracy: ± (5 % + 2 nA)
Capacitance measurement Range: 0.01 μF to 15.00 μF
Accuracy: ± (15 % rdg + 0.03 μF)
Timer Range: 0 to 99 minutes
Resolution: Setting: 1 minute, Indication: 1 second
Live circuit warning Warning range: 30 V to 660 V ac/dc, 50/60 Hz
Voltage accuracy: ± (15 % + 2 V)
Software specifications FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8

 

Model NameDescription
FLUKE-1555 10 KV INSULATION TESTER
FLUKE-1550C Fluke 1550C 5 kV Insulation Tester
Includes:
  • Test cables with alligator clips (red, black, green)
  • Infrared adapter with interface cable
  • FlukeView® Forms Basic CD-ROM
  • AC power cord
  • Soft carrying case
  • English manual
  • User's manual on CD-ROM
  • Quick reference card
  • Software license agreement
  • Registration card
  • FlukeView® Forms installation guide
  • USB-IR cable installation guide

 

Untuk keterangan lebih lanjut, silahkan download PDF ini :

Ulasan

/5
Ulasan
5
4
3
2
1

Foto dari Pembeli

Ulasan dari Pembeli

Filter
Semua
Dengan Foto
5
4
3
2
1
Telepon
Request a Quote
Produk Siap di Pesan
Rp 0
1
Bendera Indonesia Indonesia  |  Bendera Inggris English
Ingin menghubungi kami?
Klik tombol dibawah
Logo IDT
Chatbot